Connection
5.2 EMC-compliant installation
PM250 Power Module
Hardware Installation Manual, 01/2016, A5E36265179B-AA
41
5.2.3
Installing the converter in compliance with EMC rules
Rules for cable installation to ensure EMC
Install the inverter on a metal mounting plate. The mounting plate must be unpainted and
highly electrically conductive.
Use shielded cables for the following connections:
Motor and motor temperature sensor
Braking resistor (not available for all inverters)
Fieldbus
Inputs and outputs of the terminal strip
Connect the cable shields to ensure EMC:
Image 5-4 Examples of correct EMC-compliant shield connection
Example
EMC
-compliant wiring for connecting the line
supply and motor
- as well as for the Control
Unit.
Line feeder cable
- non-shielded - with
strain relief using cable ties
shielded motor cable with hose clamp for
shielding and strain relief
Shielded cable for the Control Unit with
shielding using a serrated strip on the CU
shield plate.