WARNING
Risk of electric shock and fire from supply networks with an excessively low impedance
Excessively high short-circuit currents can lead to the protective devices not being able to 
interrupt these short-circuit 
currents and being destroyed, and thus causing electric shock or 
a fire.
● Ensure that the prospective short-circuit current at the line terminal of the inverter does not 
exceed the breaking capacity (SCCR or Icc) of the protective device used.
WARNING
Electric shock if there is no ground connection 
For missing or incorrectly implemented protective conductor connection for devices with 
protection class I, 
high voltages can be present at open, exposed parts, which when touched, 
can result in death or severe injury.
● Ground the device in compliance with the applicable regulations.  
WARNING
Electric shock due to connection to an unsuitable power supply
When equipment is connected to an unsuitable power supply, exposed components may 
carry a hazardous 
voltage. Contact with hazardous voltage can result in severe injury or death.
● Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV- 
(Protective Extra Low Voltage) output voltages for all connections and terminals of the 
electronics modules.
WARNING
Electric shock due to equipment damage
Improper handling may cause damage to equipment. For damaged devices, hazardous 
voltages 
can be 
present at the enclosure or at exposed components; if touched, this can result 
in death or severe injury. 
● Ensure compliance with the limit values specified in the technical data during transport, 
storage and operation. 
● Do not use any damaged devices.
Fundamental safety instructions
2.1 General safety instructions
Motor Modules Booksize parallel connection
10 Application Manual, 01/2020, 6SL3097-5BF00-0BP0