5.5 Step 3: Parameterizing the drive object
Note
DDS configurator
The DDS configurator in STARTER cannot be used for activating function modules in the drive
object of the Motor Modules Booksize connected in parallel.
Note
Loss of the parallel connection
Use of the
DDS configurator in STARTER for activating function modules in the drive object of
the Motor Modules Booksize connected in parallel resets the type of the drive object to a
"Vector" drive object. The parallel connection is lost and the drive configuration is no longer
consistent with the existing drive configuration with Motor Modules Booksize connected in
parallel.
Only parameterize the drive object of the Motor Module Booksize connected in parallel by
using the expert list.
Perform the commissioning again from Step 1: Restoring the factory settings (Page 35).
Procedure
1. Call up the
expert list in the drive object of the Motor Modules Booksize connected in parallel.
You will find more information about calling up the expert list in Chapter Step 2: Creating a
drive object (Page 37), item 1
2. Set the parameter p0010 "Drive commissioning parameter filter / Drv comm. par_filt" to 1 to
filter out the parameters for quick commissioning
Commissioning
5.5 Step 3: Parameterizing the drive object
Motor Modules Booksize parallel connection
Application Manual, 01/2020, 6SL3097-5BF00-0BP0 39