7. A new drive object, e.g. Vector_03 appears in the project navigator.
This is the drive object for the Motor Modules Booksize connected in parallel.
Note
Drive object
The two Motor Modules Booksize are represented by a drive object for Motor Modules
Booksize connected in parallel.
8. In the project navigator, double-click "Configuration" under the drive object.
Check the configuration of the new drive object for the following information:
The power unit type must contain the entry "Parallel connection".
The
rated current of the power unit must correspond to this value: 2·0.95·rated current of
the type of the Motor Modules Booksize connected in parallel
The rated power of the power unit must correspond to this value: 2·0.95·rated power of
the type of the Motor Modules Booksize connected in parallel
If you do net get these values, repeat the commissioning from Step 1: Restoring the factory
settings (Page 35).
Commissioning
5.4 Step 2: Creating a drive object
Motor Modules Booksize parallel connection
38 Application Manual, 01/2020, 6SL3097-5BF00-0BP0