One-sided overload response
P290 must be assigned to "1" (= no reduction and shutdown when overload threshold is
reached) to prevent one-sided overload responses of the power supply units.
Pulse enable
The "Pulse enable"
inputs of the parallel Motor Modules Booksize must be wired in parallel to
achieve simultaneous release of both Motor Modules Booksize.
Safety Integrated
The Safety Integrated functions for the Motor Modules Booksize connected in parallel are not
enabled.
Hardware
4.1 Technical requirements
Motor Modules Booksize parallel connection