4. Click "Close".
5. Select the drive object "S120_CU320_2_DP" in the project navigator.
6. With the right mouse button, select the shortcut menu "Target device > Restore factory
settings".
7.
Confirm the query with "OK".
The PG/PC sets the drive parameters to their factory settings.
The new status is automatically transferred to the Control Unit memory card using the
function "Copy RAM to ROM".
8. Select the drive unit in the project navigator and call the shortcut menu
"Target device > Copy RAM to ROM".
The factory settings have now been restored: The drive is in a defined basic state.
Commissioning
5.3 Step 1: Restoring the factory settings
Motor Modules Booksize parallel connection
36 Application Manual, 01/2020, 6SL3097-5BF00-0BP0