3.1 Visual inspection
The visual inspection is performed to ensure that the drive complies with the requirements of
the order. The individual test steps are performed with the drive in a no-voltage condition.
The test together with the customer – or his representative – is carried out with the drive
installed and labeled. The results of all of the tests are documented in the acceptance report.
The SINAMICS SL150 drive consists of the following components:
Power section
Control cabinet
Excitation unit
An order can contain one or more components. During the visual inspection, all the ordered
components are individually inspected and documented.
3.1.1 Rating plate
Fundamentals
The technical data and ordered options on the rating plate and the routine test certificate are
checked to ensure that they match up.
Test procedure
1. The data on the rating plate and the routine test certificate are visually compared.
Result
The test is passed if the data match up.
3.1.2 Housing degree of protection
Fundamentals
A check is made as to whether the housing degree of protection ordered complies with what is
described in the catalog.