Loading...
W DC- DC+
DI 1
DI 2
DI 3
DI 4
DI C
24V
0V
D0 1+
DO 1-
DO2
NC
DO2
NO
DO2
C
UV
10V
AI 1
AI 2
AO 1
0V
P+
N–
Easy Start Guide
Page 12
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright The Inverter©
Drive Supermarket and must not be reproduced or altered without prior written permission.
11. How to configure “3-Wire” control with Run/Stop
pushbuttons and Forward/Reverse selection
The procedure described in Section 7 enable
Run/Stop operation via the red and green
buttons on the Inverter.
If this is unsuitable for the application, remote
switches can be used instead.
This section explains how to enable 3-wire
control with Run and Stop commands via
separate pushbuttons and Forward/Reverse
selection via a selector switch.
11.1 Parameters to change for remote 3-wire control
11.2 Connecting the Switches
A wiring diagram is shown in the illustration
opposite. The 24V terminal is a common
connection for terminals DI1, DI2 and DI3.
Note that DIC and 0V must be linked (blue
wire).
For “Run” and “Stop”, two suitable
pushbuttons should be installed. The “Run”
pushbutton should include a Normally Open
contact between terminals 24V and DI2 and
the “Stop” a Normally Closed contact between
terminals 24V and DI1.
For “Forward/Reverse” a suitable 2 position
NO (Normally Open) switch should be installed
between terminals 24V and DI3. A momentary
connection between 24V and DI2 will start the
motor. It will continue to run until the
connection between 24V and DI1 is broken.
Note that the Forward/Reverse switch only
selects the direction of rotation - it will not start
or stop the motor. If the application only
requires the motor to turn in one direction, the
Forward/Reverse switch can be omitted.
12 14
Pushbutton
Normally Open
“Run”
R
Pushbutton
Normally Closed
“Stop”
Switch, 2 Position
Normally Open
“Forward / Reverse”
13
Siemens V20 Series Inverter
Parameter
Description
How to set
P0003
User access level
Set to to allow access to extended parameters.2
P0700
Selection of command source
Set value to for terminals as command source (select index first if prompted).2 in000
P0701
Function of digital input 1
Set value to for OFF1/hold (select index first if prompted).2 in000
P0702
Function of digital input 2
Set value to for ON pulse (select index first if prompted).1 in000
P0703
Function of digital input 3
Set value to for reverse selection (select index first if prompted)..12 in000
P0727
Selection of 2/3-wire method
Set value to for 3-wire control with fwd/rev selection (select index first if prompted)..3 in000
1
2
3
4
[Order Codes 21689, 21688, 21725, 21694, 21690 x 2]