SIPART DR19
62 C73000-B7474-C140-06
Configuring Quick Reference
S10 Input signal AI3 (slop 1) with UNI module (only effective when
S9 = 4/5/6/7)
[0]
1
2
U[mV] (linear), with range plug I [mA] or U [V]
Thermocouple with internal reference junction
Thermocouple with external reference junction
3
4
5
Pt100 4-wire connection
Pt100 3-wire connection
Pt100 2-wire connection
6
7
Resistance transmitter with R < 600
Resistance transmitter with R < 2,8 k
S11 Thermocouple type AI3 (slot 2) with UNI module
(only effective if S10 = 1/2)
[0]
1
2
3
4
5
6
7
8
9
10
Type L
Type J
Type K
Type S
Type B
Type R
Type E
Type N
Type T
Type U
Any type (without linearization)
Take square roof of AI1 to AE3
no yes
S12
S13
S14
AI1 [0] 1
AI2 [0] 1
AI3 [0] 1
Allocation of x1, x2, x3, yN, yR, z to AI1A to AI3A
0 % AI1 AI2 AI3A
S15
S16
S17
S18
S19
S20
x1 0 [1] 2 3
x2 0 1 [2] 3
x3/wE 0 1 2 [3]
yN [0] 1 2 3
yR [0] 1 2 3
z[0] 1 2 3