SIPART DR19
C73000-B7474-C140-06
65
Quick Reference Configuring
S50 Priority N or H
[0]
1
N
H
S51 Manual mode in case of transmitter fault
[0]
1
2
No switchover (display only)
Manual mode beginning with most recent y
Manual mode beginning with ys
S52 Switchover manual/automatic via
Hand button Hi Control signal H
e
Interlocking He
ES
[0]
1
2
3
1)
4
1)
yes yes / static with
no yes / static with
no switchover manual operation
yes yes / dynamic with
yes yes / dynamic without
1)
as of software version -A7
S53 Iy shutdown in tracking mode (K controller only)
[0]
1
Without
With
S54 Limiting of manipulated variable YA/YE
[0]
1
Only effective in automatic mode
Effective in all modes
S55 Manipulated variable display
[0]
1
2
3
Controller output y
Position feedback yR
Split range y1/y2, with two-point controller heating/ cooling
No display
S56 Direction of action of manipulated variable display yAn
[0]
1
Normal: yAn=y
Reverved: yAn=100 % - y
Config.
switch
Setting Function
OUTPUT SWITCHOVERy DISPLAY