EasyManua.ls Logo

Siemens SIPART DR19 - Page 65

Siemens SIPART DR19
94 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIPART DR19
C73000-B7474-C140-06
65
Quick Reference Configuring
S50 Priority N or H
[0]
1
N
H
S51 Manual mode in case of transmitter fault
[0]
1
2
No switchover (display only)
Manual mode beginning with most recent y
Manual mode beginning with ys
S52 Switchover manual/automatic via
Hand button Hi Control signal H
e
Interlocking He
ES
[0]
1
2
3
1)
4
1)
yes yes / static with
no yes / static with
no switchover manual operation
yes yes / dynamic with
yes yes / dynamic without
1)
as of software version -A7
S53 Iy shutdown in tracking mode (K controller only)
[0]
1
Without
With
S54 Limiting of manipulated variable YA/YE
[0]
1
Only effective in automatic mode
Effective in all modes
S55 Manipulated variable display
[0]
1
2
3
Controller output y
Position feedback yR
Split range y1/y2, with two-point controller heating/ cooling
No display
S56 Direction of action of manipulated variable display yAn
[0]
1
Normal: yAn=y
Reverved: yAn=100 % - y
Config.
switch
Setting Function
OUTPUT SWITCHOVERy DISPLAY

Other manuals for Siemens SIPART DR19

Related product manuals