A.9 Information List
601
7UT613/63x Manual
C53000-G1176-C160-2
5010 >BLOCK fuse failure monitor
(>FFM BLOCK)
Supervision SP ON
OFF
ON
OFF
* LED BI BO 71 7 1 Yes
5083 >BLOCK reverse power protec-
tion (>Pr BLOCK)
Reverse Power SP * * * LED BI BO
5086 >Stop valve tripped (>SV tripped) Reverse Power SP ON
OFF
ON
OFF
* LED BI BO 70 77 1 Yes
5091 Reverse power prot. is switched
OFF (Pr OFF)
Reverse Power OUT ON
OFF
**LEDBO70811Yes
5092 Reverse power protection is
BLOCKED (Pr BLOCKED)
Reverse Power OUT ON
OFF
ON
OFF
* LED BO 70 82 1 Yes
5093 Reverse power protection is
ACTIVE (Pr ACTIVE)
Reverse Power OUT ON
OFF
**LEDBO70831Yes
5096 Reverse power: picked up (Pr
picked up)
Reverse Power OUT * ON
OFF
m LED BO 70 84 2 Yes
5097 Reverse power: TRIP (Pr TRIP) Reverse Power OUT * ON m LED BO 70 85 2 Yes
5098 Reverse power: TRIP with stop
valve (Pr+SV TRIP)
Reverse Power OUT * ON m LED BO 70 86 2 Yes
5099 Reverse pwr err: CT fact too
large/small (Pr CT Fact ><)
Reverse Power OUT ON * * LED BO
5100 Reverse power err: Allocation of
VT (Pr VT error)
Reverse Power OUT ON * * LED BO
5101 Reverse pwr err:Not avail. for this
obj. (Pr obj. error)
Reverse Power OUT ON * * LED BO
5113 >BLOCK forward power supervi-
sion (>Pf BLOCK)
Forward Power SP * * * LED BI BO
5116 >BLOCK forw. power superv. Pf<
stage (>Pf< BLOCK)
Forward Power SP ON
OFF
ON
OFF
* LED BI BO 70 102 1 Yes
5117 >BLOCK forw. power superv. Pf>
stage (>Pf> BLOCK)
Forward Power SP ON
OFF
ON
OFF
* LED BI BO 70 103 1 Yes
5121 Forward power supervis. is
switched OFF (Pf OFF)
Forward Power OUT ON
OFF
* * LED BO 70 106 1 Yes
5122 Forward power supervision is
BLOCKED (Pf BLOCKED)
Forward Power OUT ON
OFF
ON
OFF
* LED BO 70 107 1 Yes
5123 Forward power supervision is
ACTIVE (Pf ACTIVE)
Forward Power OUT ON
OFF
* * LED BO 70 108 1 Yes
5126 Forward power: Pf< stage picked
up (Pf< picked up)
Forward Power OUT * ON
OFF
m LED BO 70 109 2 Yes
5127 Forward power: Pf> stage picked
up (Pf> picked up)
Forward Power OUT * ON
OFF
m LED BO 70 110 2 Yes
5128 Forward power: Pf< stage TRIP
(Pf< TRIP)
Forward Power OUT * ON m LED BO 70 111 2 Yes
5129 Forward power: Pf> stage TRIP
(Pf> TRIP)
Forward Power OUT * ON m LED BO 70 112 2 Yes
5130 Forward pwr err: CT fact too
large/small (Pf> CT fact ><)
Forward Power OUT ON * * LED BO
5131 Forward power error: VT assign-
ment (Pf> VT error)
Forward Power OUT ON * * LED BO
5132 Forward pwr err:Not avail. for this
obj. (Pf> Object err)
Forward Power OUT ON * * LED BO
5143 >BLOCK I2 (Unbalance Load)
(>BLOCK I2)
Unbalance Load SP * * * LED BI BO 70 126 1 Yes
5145 >Reverse Phase Rotation (>Re-
verse Rot.)
P.System Data 1 SP ON
OFF
**LEDBIBO71341Yes
5146 >Reset memory for thermal
replica I2 (>RM th.rep. I2)
Unbalance Load SP * * * LED BI BO 70 127 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation