EasyManua.ls Logo

Siemens SIPROTEC 7UT635*-* N series - Page 602

Siemens SIPROTEC 7UT635*-* N series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A Appendix
602
7UT613/63x Manual
C53000-G1176-C160-2
5147 Phase Rotation L1L2L3 (Rotation
L1L2L3)
P.System Data 1 OUT ON
OFF
* * LED BO 70 128 1 Yes
5148 Phase Rotation L1L3L2 (Rotation
L1L3L2)
P.System Data 1 OUT ON
OFF
* * LED BO 70 129 1 Yes
5151 I2 switched OFF (I2 OFF) Unbalance Load OUT ON
OFF
* * LED BO 70 131 1 Yes
5152 I2 is BLOCKED (I2 BLOCKED) Unbalance Load OUT ON
OFF
ON
OFF
* LED BO 70 132 1 Yes
5153 I2 is ACTIVE (I2 ACTIVE) Unbalance Load OUT ON
OFF
* * LED BO 70 133 1 Yes
5157 Unbalanced load: Thermal
warning stage (I2 th. Warn)
Unbalance Load OUT ON
OFF
* * LED BO 70 135 2 Yes
5158 Reset memory of thermal replica
I2 (RM th.rep. I2)
Unbalance Load OUT ON
OFF
ON
OFF
* LED BO 70 137 1 Yes
5159 I2>> picked up (I2>> picked up) Unbalance Load OUT * ON
OFF
* LED BO 70 138 2 Yes
5160 Unbalanced load: TRIP of current
stage (I2>> TRIP)
Unbalance Load OUT * ON LED BO
5161 Unbalanced load: TRIP of
thermal stage (I2 Θ TRIP)
Unbalance Load OUT * ON LED BO
5165 I2> picked up (I2> picked up) Unbalance Load OUT * ON
OFF
* LED BO 70 150 2 Yes
5166 I2p picked up (I2p picked up) Unbalance Load OUT * ON
OFF
* LED BO 70 141 2 Yes
5167 Unbalanced load: Pick-up I2
thermal (I2th Pick-up)
Unbalance Load OUT * ON
OFF
* LED BO 70 142 2 Yes
5168 I2 err.: adverse Adaption factor
CT (I2 Adap.fact.)
Unbalance Load OUT ON * * LED BO
5170 I2 TRIP (I2 TRIP) Unbalance Load OUT * ON m LED BO 70 149 2 Yes
5172 I2 err.: Not available for this
object (I2 Not avail.)
Unbalance Load OUT ON * * LED BO
5178 I2> TRIP (I2> TRIP) Unbalance Load OUT * ON LED BO
5179 I2p TRIP (I2p TRIP) Unbalance Load OUT * ON LED BO
5203 >BLOCK frequency protection
(>BLOCK Freq.)
Frequency Prot. SP * * * LED BI BO 70 176 1 Yes
5211 Frequency protection is switched
OFF (Freq. OFF)
Frequency Prot. OUT ON
OFF
* * LED BO 70 181 1 Yes
5212 Frequency protection is
BLOCKED (Freq. BLOCKED)
Frequency Prot. OUT ON
OFF
ON
OFF
* LED BO 70 182 1 Yes
5213 Frequency protection is ACTIVE
(Freq. ACTIVE)
Frequency Prot. OUT ON
OFF
* * LED BO 70 183 1 Yes
5214 Frequency protection undervolt-
age Blk (Freq UnderV Blk)
Frequency Prot. OUT ON
OFF
ON
OFF
* LED BO 70 184 1 Yes
5254 Frequency protection: error VT
assign. (Freq. error VT)
Frequency Prot. OUT ON * * LED BO
5255 Frequency prot.:Not avail. for this
obj. (Freq. err. Obj.)
Frequency Prot. OUT ON * * LED BO
5353 >BLOCK overexcitation protec-
tion (>U/f BLOCK)
Overexcit. SP * * * LED BI BO
5357 >Reset memory of thermal
replica U/f (>RM th.rep. U/f)
Overexcit. SP * * * LED BI BO
5361 Overexcitation protection is
swiched OFF (U/f> OFF)
Overexcit. OUT ON
OFF
**LEDBO71831Yes
5362 Overexcitation protection is
BLOCKED (U/f> BLOCKED)
Overexcit. OUT ON
OFF
ON
OFF
* LED BO 71 84 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents