SIRIUS 3RT2 contactors/contactor assemblies   
2.8 Technical data 
  SIRIUS Innovations 
244  System Manual, 01/2011, A8E56203870002-03 
Type  3RT2023  3RT2024  3RT2025  3RT2026  3RT2027  3RT2028 
Size  S0  S0  S0  S0  S0  S0 
General data 
Degree of protection to EN 60947-1, 
Annex C 
  IP20, drive system IP40 
Touch protection acc. to DIN EN 50274    Finger-safe 
  AC operation 
g/ms  7.5/5 and 4.7/10  8.3/5 and 5.3/10 Shock resistance 
rectangular pulse 
  DC operation 
g/ms  > 10/5 and > 7.5/10 
  AC operation 
g/ms  11.8/5 and 7.4/10  13/5 and 8.3/10 Shock resistance 
sine pulse 
  DC operation 
g/ms  > 15/5 and > 10/10 
Conductor cross-sections 
2)
 
1) 
  Contact service life for main contacts is listed in the table titled "Contact service life of auxiliary and main contacts". 
2)
  Conductor cross-sections are listed in the table titled "Conductor cross-sections - 3RT202.". 
 
Table 2- 85  Short-circuit protection for 3RT202. contactors without overload relay 
Type  3RT2023  3RT2024  3RT2025  3RT2026  3RT2027  3RT2028 
Size  S0   
Short-circuit protection for contactors without overload relay 
Main circuit 
  Fuse links gL/gG NH 3NA, DIAZED 5SB, 
NEOZED 5SE acc. to 
IEC 60947-4-1/DIN EN 60947-4-1 
 
- Type of coordination "1"  A  63  100  125 
- Type of coordination "2"  A  25  35  50 
 
- Weld-free
1)
  A  10  16  15 
  Miniature circuit breaker with C 
characteristic (short-circuit current 
3 kA, type of coordination "1") 
A  25  32  40 
Auxiliary circuit 
  Fuse links gL/gG DIAZED 5SB, 
NEOZED 5SE (weld-free fuse 
protection I
k
 ≥ 1 kA) 
A  10 
  Miniature circuit breakers with C 
characteristic (short-circuit 
current I
k
 < 400 A) 
A  10 
1)
  Test conditions in accordance with IEC 60947-4-1.