SIRIUS 3RV2 motor starter protectors 
  4.9 Accessories 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
419 
4.9.6  Disconnector module 
4.9.6.1  Description 
Disconnector module  
The disconnector module is mounted on the motor starter protector on the infeed side. The 
disconnector module can be used to form a visible isolating distance. To set up the isolating 
distance, the plug connector is removed from the enclosure. The isolating plug can only be 
removed with the supply disconnected.  
The touch-proof isolating point is clearly visible and is secured with a padlock so that the 
plug connector cannot be inserted during maintenance work, for example.  
The disconnector module is compatible for use with all motor starter protector sizes. 
 
 
Note 
 
  The disconnector module cannot be used with 3RV27 and 3RV28 circuit breakers. 
  The disconnector module covers the connection screws on the transverse auxiliary 
switch. Therefore, if you are using the disconnector module, we recommend that you use 
the lateral auxiliary switches or wait until the transverse auxiliary switches have been 
wired before mounting the disconnector module. 
  The disconnector module must not be used in conjunction with the 3-phase busbar 
3RV1915. 
 
4.9.6.2  Mounting 
Mounting sequence 
 
 
Note 
Mounting sequence for disconnector module and transverse auxiliary switch 
The disconnector module covers the connection screws on the transverse auxiliary switch. 
Therefore, we recommend that you use the lateral auxiliary switches or wait until the 
transverse auxiliary switches have been wired before mounting the disconnector module.