SIRIUS 3RU2/3RB3 overload relays 
  5.4 Functions 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
499 
5.4.2  Ground-fault protection (3RB31 only) 
Introduction 
In addition to current-dependent protection for loads against impermissibly high temperature 
rise caused by overload, phase asymmetry, and phase failure, 3RB31 solid-state overload 
relays feature internal ground-fault detection (not possible in conjunction with contactor 
assemblies for star-delta (wye-delta) start). This provides protection of loads against high-
impedance faults to ground caused by damaged insulation, moisture, condensation, etc. 
Ground-fault protection 
In the event of a ground fault, the device trips immediately, disconnecting the contactor (and 
thus the load) by means of the auxiliary contacts. To also protect the load and the system 
against ground faults caused by damaged insulation, moisture, condensation, etc., the 
overload relays support ground-fault monitoring by means of internal ground-fault detection. 
 
 
Note 
Contactor assembly for star-delta (wye-delta) start 
Internal ground-fault detection is not possible with contactor assemblies star-delta (wye-
delta) start. 
 
 
Table 5- 6  Ground-fault detection 
Type of ground-fault detection  Application 
Internal ground-fault detection  For motors with three-wire connection for the detection of fault 
currents ≥ 75 % of the current setting I
e
 in operation