SIRIUS 3RU2/3RB3 overload relays   
5.4 Functions 
  SIRIUS Innovations 
494  System Manual, 01/2011, A8E56203870002-03 
5.4  Functions 
5.4.1  Protection against overload, phase failure, and phase asymmetry 
5.4.1.1  Functional principle 
Overload relays are used for the current-dependent protection of electrical consumers 
(such as motors) against excessive temperature rises, which may be caused by overloading, 
asymmetrical power consumption, a phase failure in the line supply conductor or a locked 
rotor. 
In the event of an overload, phase asymmetry or a phase failure, or if a rotor locks, the motor 
current will rise beyond the set rated motor current. This increased current - which, if 
sustained over a long period, may damage or even destroy the load - is detected by the 
overload relay and evaluated with the assistance of a thermal motor model. 
Two functional principles are possible here:  
●  Thermal 
●  Solid-state 
Functional principle of 3RU21 thermal overload relays 
The current rise caused by the overload causes increased heat rise affecting the heating 
elements. The bimetals respond by deflecting, and actuate the auxiliary contacts via the 
release mechanism. 
Functional principle of 3RB30/3RB31 solid-state overload relays 
The current rise is detected by the integrated current transformers and evaluated by 
corresponding solid-state circuits which then supply a pulse to the auxiliary contacts. The 
contactor and the load are disconnected via the auxiliary contacts. 
 
 
Note 
Protection of DC loads and single-phase AC loads 
Only 3RU21 thermal overload relays can provide an assurance of protecting DC loads and 
single-phase AC loads against overload. 
If a 3RU21 thermal overload relay is to be used to protect DC loads or single-phase AC 
loads, all the bimetal strips have to be heated. Therefore, all of the relay's main current paths 
have to be connected in series. 
 
Phase-failure protection 
3RU21 thermal overload relays and 3RB30/3RB31 solid-state overload relays feature phase 
loss sensitivity (see the chapter titled Tripping characteristics (Page 496)) to minimize load 
temperature rise in two
-phase operation.