4.9.6.3  Isolation and shut-off 
Creating and securing the isolating distance  
Table 4- 21  Creating and securing the isolating distance 
Step  Operating instruction  Figure 
1  Set the rotary button on the motor 
starter protector to O. 
2  Slide the closing lockout down. 
3  Slide the isolating plug forward and 
out of the disconnector module. 
 
4  Slide the closing lockout up. 
5  Secure the closing lockout so that the 
isolating plug cannot be inserted or 
pushed further in.