SIRIUS 3RR2 current monitoring relays   
8.10 Technical data 
  SIRIUS Innovations 
746  System Manual, 01/2011, A8E56203870002-03 
8.10.3.2  Main circuit 
Table 8- 24  Technical data for the main circuit, 3RR21 current monitoring relay 
Type  3RR22 41  3RR22 42 
Size  S00  S0 
Width  45 mm  45 mm 
Rated insulation voltage U
i
 
(pollution degree 3) 
V  690 
Rated impulse withstand voltage U
imp
 kV 6 
Rated operational voltage U
e
  V  690 
Relative measuring accuracy % 5 
Current carrying capacity 
  for permanent overcurrent 
A  max. 16  max. 40 
  for overcurrent < 1 s 
A  max. 320  max. 800 
Type of current 
  Alternating current 
Hz  50 / 60 
Current setting  A  1.6 ... 16  4 to 40 A 
Power loss per device (max.)  W  2.5 
Short-circuit protection 
  With fuse without contactor 
See "Selection and ordering data" in Catalog 
LV 1 N SIRIUS Innovations. 
  With fuse and contactor 
See the chapter titled "Motor starter protectors (Page 379)"