SIRIUS 3RT2 contactors/contactor assemblies   
2.8 Technical data 
  SIRIUS Innovations 
246  System Manual, 01/2011, A8E56203870002-03 
Type  3RT2023...25  3RT2026...28 
Size  S0 
Actuation 
Switching times at 0.8 to 1.1 x U
S
1)
 
Total break time = opening delay + arcing time 
  AC operation 
- Closing delay  ms  9 ... 38  8 ... 40  
- Opening delay  ms  4 ... 16 
  DC operation 
- Closing delay  ms  50 ... 170  50 ... 170  
- Opening delay  ms  15 ... 17.5 
  Arcing time 
ms  10 
Switching times at 1.0 x U
s
1)
 
  AC operation 
- Closing delay  ms  10 ... 18  10 ... 17  
- Opening delay  ms  4 ... 16 
  DC operation 
- Closing delay  ms  55 ... 80  
- Opening delay  ms  16 ... 17 
1)
  The OFF-delay times of the NO contacts and the ON-delay times of the NC contacts increase if the contactor coils are 
attenuated against voltage peaks (varistor + 2 ms to 5 ms, diode combination: 2x to 6x). 
 
Table 2- 87  Actuation - 3RT202.-.NB3, 3RT202.-.NF3, 3RT202.-.NP3 contactors 
Type  3RT202.-.NB3  3RT202.-.NF3  3RT202.-.NP3 
Size  S0 
Actuation 
Magnet coil operating range AC/DC  0.7 to 1.3 x U
S
 
Magnet coil power input (for cold coil and 1.0 x U
S
)   
  AC operation, 50 Hz, UC version 
- Switch-on power  VA  6.5/5.7  13.6/13.2  16.1/15.9 
- cos ϕ    0.98/0.96  0.98/0.99  0.99/0.99 
- Holding power  VA  1.26/1.3  1.91/1.9  3.41/3.58 
 
- cos ϕ    0.78/0.8  0.61/0.61  0.36/0.45 
  DC operation, UC version 
- Switch-on power  W  6.7  13.2  15  
- Holding power  W  0.8  1.56  1.83 
Permissible residual current of electronics (with 0 signal) 
  AC operation 
mA  < 7 mA x (230 V/U
S
) 
  DC operation 
mA  < 16 mA x (24 V/U
S
)