SIRIUS 3RT2 contactors/contactor assemblies 
  2.8 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
269 
3RT20 coupling relays for switching motors 
Technical data for 3RT20 coupling relays 
Unless listed below, the technical data is the same as that for 3RT20 contactors for switching 
motors. 
Table 2- 108  General data and actuation for coupling relays 3RT201.-..B4. and 3RT202.-..B4. 
Type  3RT201.-.HB4.  3RT201.-.JB4.  3RT201.-.KB4.  3RT202.-.KB4. 
Size  S00  S0 
General data 
Mechanical durability  Operat
ing 
cycles 
30 million  10 million 
Protective separation between coil and 
main contacts acc. to DIN EN 60947-1, 
Annex N 
V  400 
Actuation 
Magnet coil operating range  0.7 to 1.25 x U
S
 
At U
S
 17 V  W  1.4  2.3 
24 V  W  2.8  4.5 
Magnet coil power 
input  
(for cold coil) 
Switch-on power = 
holding power 
30 V  W  4.4  7 
Permissible residual current 
of electronics (with 0 signal) 
mA  < 10 mA x (24 V/U
S
)  < 6 
mA x (24 V/U
S
) 
Magnet coil suppressor circuit  Without 
overvoltage 
attenuation 
 
With diode 
 
Suppressor 
diode 
 
With varistor 
8
 
Operating times for coupling relays 
  Switching on 
ON-delay NO  ms  40 ... 130  70 ... 270 - At 17 V 
OFF-delay NC  ms  30 ... 80  60 ... 250 
ON-delay NO  ms  35 ... 60  65 ... 90 - At 24 V 
OFF-delay NC  ms  25 ... 40  55 ... 80 
ON-delay NO  ms  25 ... 50  52 ... 65 
 
- At 30 V 
OFF-delay NC  ms  15 ... 30  43 ... 57 
  Switching off at 17 to 30 V 
OFF-delay NO  ms  7 ... 20  38 ... 65  7 ... 20  19 ... 21  
ON-delay NC  ms  20 ... 30  55 ... 75  20 ... 30  25 ... 31