SIRIUS 3RV2 motor starter protectors 
  4.10 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
465 
Up to 240 V AC  Up to 400 V
2)
/415 V
3)
 AC Rated current I
n
 
I
cuIT
  Max. fuse (gL/gG)
4)
 I
cuIT
  Max. fuse (gL/gG)
4), 5)
 
A  kA  A  kA  A 
Size S0 
16  55  80  4  63 
20  55  80  4  63 
22  55  80  4  63 
25  55  80  4  63 
28  55  80  2  63 
32  55  80  2  63 
36  20  80  2  63 
40  20  80  2  63 
1)
  No backup fuse required, as short-circuit-proof up to 100 kA 
2)
  10 % overvoltage 
3)
  5 % overvoltage 
4)
  Backup fuse only required if short-circuit current at installation location is > I
cuIT
 
5)
  Alternatively, fuseless limiter combinations can be used for 690 V AC 
 
Table 4- 35  Short-circuit breaking capacity I
cuIT
 in the IT system part 2 
Up to 440 V
2)
/460 V
3)
 AC  Up to 500 V
2)
/525 V
3)
 AC  Up to 690 V
6)
 AC Rated current I
n
 
I
cuIT
  Max. fuse 
(gL/gG)
4), 5)
 
I
cuIT
  Max. fuse (gL/gG)
4), 5)
 I
cuIT
  Max.  
fuse 
(gL/gG)
4)
 
A  kA  A  kA  A  kA  A 
Size S00 
0.16 ... 0.4  100 
1)
  100 
1)
  100 
1)
 
0.5  100 
1)
  100 
1)
 0.5 4 
0.63  100 
1)
  100 
1)
 0.5 6 
0.8  100 
1)
  100 
1)
 0.5 6 
1  8  10  8  10  2  10 
1.25  8  16  8  16  2  16 
1.6  8  20  8  20  2  16 
2  8  25  8  25  2  20 
2.5  8  25  8  25  2  20 
3.2  8  32  8  32  2  25 
4  2  32  2  32  2  25 
5  2  32  2  32  2  25 
6.3  2  40  2  40  1.5  35 
8  2  40  2  40  1.5  35 
10  2  40  2  40  1.5  40 
12.5  2  50  2  50  1.5  40 
16  2  50  2  50  1.5  40