SIRIUS 3RV2 motor starter protectors 
  4.10 Technical data 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
473 
"Self-protected combination motor controller (type E)" (up to 32 A) 
3RV20 motor starter protector as "Self-Protected Combination Motor Controller (Type E)" 
For approval according to UL 508, a clearance of 1 inch and a creepage distance of 2 inches 
are required on the line side for a "Self-Protected Combination Motor Controller". 
Therefore, 3RV20 motor starter protectors in size S00/S0 are approved according to UL 508 
together with the terminal block (order no. 3RV29 28-1H) or phase barriers (order 
no. 3RV2928-1K). 
CSA approval does not require extended clearances and creepage distances. The terminal 
blocks or phase barriers can, therefore, be omitted for use as a "Self-Protected Combination 
Motor Controller" according to the CSA. 
3RV20 motor starter protectors are approved as "Self-Protected Combination Motor 
Controller" under the following file numbers:  
●  UL File No. E156943, CCN: NKJH. 
●  CSA Master Contract 165071, Product Class: 3211 08. 
 
Motor starter protector  hp-rating
1) 
for FLA
2) 
 
max. 
Type  V  1-phase  3-phase 
Size S00 
3RV20 11 
115  1  2 
200  2  3 
230  2  5 
460  --  10 
FLA
2) 
max.  
16 A, 480 V 
12.5 A, 600 V 
575 / 600  --  10 
Size S0 
3RV20 21 
115  2  5 
200  3  7 1/2 
230  5  10 
460  --  20 
FLA
2) 
max. 
32 A, 480 V 
575/600  --  -- 
1)
  hp-rating= power in horse power(maximum motor power). 
2)