SIRIUS 3RU2/3RB3 overload relays 
  5.4 Functions 
SIRIUS Innovations 
System Manual, 01/2011, A8E56203870002-03 
497 
Tripping characteristic curves for the 3RU21 thermal overload relay 
The tripping characteristic curve for the 3RU21 thermal overload relay loaded at 3 poles (see 
the figure below) applies subject to the prerequisite that all three bimetal strips are loaded 
with the same current at the same time. If only two bimetal strips are heated following a 
phase failure, these two strips alone have to generate the force required to trigger the 
release mechanism and would need a longer tripping time or a higher current if no additional 
action was taken. If these higher currents are applied over a longer period of time, they 
usually cause damage to the load. To avoid damage, 3RU21 overload relays feature phase 
loss sensitivity, which uses a corresponding mechanism to induce accelerated tripping in 
accordance with the characteristic curve for 2-pole loading from the cold state. 
Compared with a cold load, a load at operating temperature obviously has a lower 
temerature reserve. 3RU21 thermal relays take account of this fact by reducing the tripping 
time to approximately a quarter following prolonged loading with the setting current I
e
. 
1
2
,>$@
W>V@
  
PLQ
 
t [s]  Tripping time 
I [A]  Current 
1  3-pole load 
2  2-pole load 
Figure 5-3  Time-current characteristic curve, schematic diagram