SIRIUS 3RR2 current monitoring relays   
8.8 Operation 
  SIRIUS Innovations 
722  System Manual, 01/2011, A8E56203870002-03 
Blocking current monitoring 
Definition of blocking current monitoring (n x I▲)  
If the load current overshoots the value of the set threshold value for current overshoot (I▲) 
by n times during operation, a blocking current error has occurred. Any delay times which 
are running (Del) are aborted and both the CO contact and the semiconductor output change 
their switching state. 
Setting range 
The setting range for blocking current monitoring is No (off) or 2 to 5 x I▲. The increment is 
1 x I▲. 
Factory setting 
Blocking current monitoring is deactivated by default (No). 
Changes to settings 
Changes to blocking current monitoring can be made using the arrow keys. Press and hold 
down the keys to speed up this process. 
Fault current monitoring 
Definition of fault current monitoring  
If fault current monitoring has been activated (I >>   = yes) and the total current of the load 
currents at terminals 1L1 / 2T1, 3L2 / 4T2 and 5L3 / 6T3 rises above the permissible 
threshold (S00: 1.5 A / S00: 4 A) all delay times which are running (onDel, RsDel, Del) are 
aborted and both the CO contact and the semiconductor output change their switching state 
immediately (≤ 200 ms). 
Factory setting 
Fault current monitoring is deactivated by default. 
Changes to settings 
Fault current monitoring can be activated and deactivated using the arrow keys.