Glossary   
 
  SIRIUS Innovations 
772  System Manual, 01/2011, A8E56203870002-03 
Soft starter 
This is a motor starter which reduces the starting torque (starting torque, break loose torque) 
and the starting current of the motor in order to decrease the vibrations experienced by the 
driven machine and to prevent current peaks in the network. The starting torque is reduced 
because the supply voltage is initially set to a value lower than the rated voltage of the motor 
(the starting torque is proportional to the square of the voltage applied). The terminal voltage 
can be increased as soon as the motor starts to run. Classic ways of reducing the terminal 
voltage are star-delta (wye-delta) start, startup via resistors in the stator, and startup with an 
auto-transformer, for example. The use of solid-state motor controllers with switched thyristor 
circuits is becoming more and more prevalent as a way of controlling the terminal voltage on 
squirrel-cage motors. See also "Soft starting" and "Soft ramp-down". 
Soft starting 
Since the motor voltage is controlled (phase control) by an electronic soft starter during the 
startup process, the consumed starting current and the starting torque generated in the 
motor are also controlled. 
Space above the arc chute 
When a switching device is being operated, particularly when highly inductive load currents 
or short-circuit currents are being switched off, the ionized gases generated by the arc are 
pressed out of the openings in the arc chute. In order to ensure that the concentration of 
these ionized gases does not reach a hazardous level, a specific clearance must be 
provided above or in front of the device. This space above the arc chute is defined by the 
manufacturer (usually on the dimension drawings) and depends on whether exposed live 
conductors (e.g. busbars), conductive structural components, and insulating partitions can 
be found on the switching device. Arc chute attachments can be mounted to larger motor 
starter protectors in order to reduce the required clearance and therefore the space required 
in the control cabinet. No space is required above the arc chute for vacuum circuit breakers 
and vacuum contactors, since the arc will not escape from the vacuum chute and no ionized 
gases will be released. 
Star-delta (wye-delta) starter 
See "Contactor assembly for star-delta (wye-delta) start". 
Starting current 
Three-phase asynchronous motors have a high direct starting current I
starting.
 Depending on 
the motor type, this current can be between three and fifteen times as high as the rated 
operational current. Seven or eight times the rated motor current can be assumed as a 
typical value. 
Starting torque 
The starting torque and the breakdown torque can usually be assumed to be between two 
and four times the rated torque. From the point of view of the load machine, this means that 
the starting and acceleration forces exert a higher mechanical load on the machine and the 
product being conveyed compared to nominal operation.