Configuration
6.5 Safety instructions for use in hazardous areas (3RB)
SIRIUS 3RU thermal overload relays / SIRIUS 3RB electronic overload relays
70 Manual, 09/2016, A5E03656507420A/RS-AB/003
Example
Motor 500 V, 50 / 60 Hz, 110 kW, 156 A, temperature class T3, TE time = 18 s, I
A
/ I
N
= 5.0
Switch-off conditions of the EEx motor, selected: CLASS 10E
Further information and certificates are available for download on the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/16027/char).
Short-circuit protection for type of coordination 2 according to EN 60947-4-1
Short-circuit protection must be provided by separately arranged overcurrent protection
devices.
NOTICE
Short-circuit protection
When combining with other contactors, observe the respective maximum fuse protection of
the contactor for type of coordination 2.
Line protection
NOTICE
Observe dimensioning of conductor cross-sections
An impermissibly high cable surface temperature must be avoided by correctly
dimensioning the cross sections.
An adequate conductor cross section must be chosen for heavy starting (CLASS 20 and
CLASS 30).

Table of Contents