Technical data
11.3 3RU21 thermal overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
109
Type
3RU2116
3RU2126
Size
S00
S0
Width
45 mm
45 mm
Repeat terminals
Coil repeat terminal
Yes Not required
Auxiliary switch repeat terminal
Yes Not required
Degree of protection
acc. to IEC 60529 IP20
Touch protection
acc. to IEC 61140 Screw connection and spring-loaded terminals: finger-safe
Ring cable lug connection: finger-safe only with optional terminal
covers
Shock resistance with sine
acc. to IEC 60068-2-27
15g / 11 ms
2)
Resistance to extreme climates - Humidity
% 90
Dimensions
See Dimension drawings for 3RU21 thermal overload relays
(Page 151)
Installation altitude above sea level
m Up to 2,000; above this, please contact us
Mounting position
See Minimum clearances and mounting position (Page 59)
Type of fixing
Contactor mounting/stand-alone assembly with terminal support
3)
1)
Remote RESET in conjunction with the appropriate accessory
2)
Auxiliary contacts 95/96 and 97/98: 8g / 11 ms.
3)
For screw and snap-on mounting onto DIN rail TH 35.