Technical data
11.3 3RU21 thermal overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
121
11.3.2.8
Mounting/fixing/dimensions
Technical data for mounting/fixing/dimensions, 3RU2136 overload relays
3RU2136-...0
3RU2136-...1
Mounting type
direct mounting stand-alone installation
mounting position
any
Depth
mm 105 117
Height
mm 90 105
Width
mm 55
Distance, to be maintained, conductive
elements
downwards
mm
10
backwards
mm 0
sidewards
mm 10
forwards
mm 10
upwards
mm 10
Distance, to be maintained, to earthed
part
downwards
mm
10
backwards
mm 0
sidewards
mm 10
forwards
mm 10
upwards
mm 10
11.3.2.9
UL/CSA rated data
Technical data - UL/CSA rated data, 3RU2136 overload relays
3RU2136-....
Operating voltage
according to UL 60947
rated value
V 600
Contact rating designation
for auxiliary contacts
according
to UL
B600 / R300