Siemens SIRIUS 3RU2 - Mounting; Mounting options for the 3 RU21, 3 RB30 and 3 RB31; Minimum clearances and mounting position

Siemens SIRIUS 3RU2
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
59
Mounting
7
7.1
Mounting options
Mounting options for the 3RU21, 3RB30 and 3RB31
The 3RU2 thermal overload relays and the 3RB3 solid-state overload relays are matched
electrically and mechanically to 3RT2 contactors. As a result, direct mounting can be
achieved easily. Alternatively, the devices are suitable for stand-alone assembly.
7.2
Minimum clearances and mounting position
Minimum clearance
A minimum lateral clearance of > 6 mm must be maintained from live and grounded parts.
Mounting position for 3RU21 thermal overload relay
The diagrams below illustrate the permissible mounting positions for contactor mounting and
stand-alone assembly for 3RU21 thermal overload relays.
Table 7- 1 Permissible mounting positions for the 3RU21
Overload relay, stand-alone assembly
Contactor + overload relay
The set value is 1.1 times the motor current for a mounting position in the hatched area.