Technical data
11.3 3RU21 thermal overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
108 Manual, 09/2014, A5E03656507420A/RS-AA/002
11.3
3RU21 thermal overload relays
11.3.1
3RU2116/3RU2126 thermal overload relays
11.3.1.1
General technical data
General technical data for 3RU2116/3RU2126 overload relays
Table 11- 6 General technical data for 3RU2116/3RU2126 overload relays
Type
3RU2116
3RU2126
Size
S00
S0
Width
45 mm
45 mm
Tripping in the event of
Overload and phase failure
Tripping class acc. to IEC/EN 60947-4-1
CLASS 10
Phase loss sensitivity
Yes
Overload warning
No
Resetting and recovery
Reset options following tripping
Manual, automatic, and remote RESET
1)
Recovery time
Depending on the level of the tripping current and the tripping
characteristic curve
Equipment
Display of operating state on device
Yes, by means of TEST function/switch position indicator slide
TEST function
Yes
RESET key
Yes
STOP button
Yes
ATEX
Suitable for overload protection of explosion-proof motors of
protection type "increased safety" Ex e
EC type examination certificate number
according to Directive 94/9/EC (ATEX)
DMT 98 ATEX G 001
Ambient temperature
Storage/transport
°C -55 ... + 80
Operation
°C -40 ... + 70
Temperature compensation
°C Up to 60
Permissible rated current for control cabinet internal temperature
- Up to 60° C % 100 (current reduction is required above +60 °C)
- 60 °C to 70 °C % 87