Technical data
11.4 3RB30/3RB31 solid-state overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
133
Main circuit
Technical data for the main circuit, 3RB303./3RB313. overload relays
Insulation
voltage
with
degree of
pollution 3
rated value
Impulse
voltage
resistance
rated
value
Voltage
type for
main
circuit
Type of
assignement
Design of the fuse
link for short-circuit
protection of the
main circuit
necessary
Operational current
for heavy
starting
CLASS 20
maximum
for heavy
starting
CLASS 30
maximum
V V A A
690 6 000 AC 2 fuse gL/gG: 160 A 25 25
690 6 000 AC 2 fuse gL/gG: 160 A 25 25
690 6 000 AC 2 fuse gL/gG: 160 A 25 25
690 6 000 AC 2 fuse gL/gG: 160 A 25 25
690 6 000 AC 2 Fuse gL/gG: 200 A 50 50
690 6 000 AC 2 Fuse gL/gG: 200 A 50 50
690 6 000 AC 2 Fuse gL/gG: 200 A 50 50
690 6 000 AC 2 Fuse gL/gG: 200 A 50 50
690 6 000 AC 2 fuse gL/gG: 250 A 60 50
690 6 000 AC 2 fuse gL/gG: 250 A 60 50
690 6 000 AC 2 fuse gL/gG: 250 A 80 80
690 6 000 AC 2 fuse gL/gG: 250 A 80 80