EasyManua.ls Logo

Siemens SIRIUS 3RU2 - Page 125

Siemens SIRIUS 3RU2
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
11.4 3RB30/3RB31 solid-state overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
125
Type
3RB301., 3RB311.
3RB302., 3RB312.
Size
S00
S0
Width
45 mm
45 mm
Electromagnetic compatibility (EMC) - Immunity
Conducted interference suppression
- Burst acc. to
IEC 61000-4-4
(corresponds to
severity 3)
kV 2 (power ports), 1 (signal ports)
- Surge acc. to
IEC 61000-4-5
(corresponds to
severity 3)
kV 2 (line to ground), 1 (line to line)
- RF coupling
according to
IEC 61000-4-6
V 10
Electrostatic discharge acc. to
IEC 61000-4-2
(corresponds to severity 3)
kV 8 (air discharge), 6 (contact discharge)
Field-related interference
suppression to IEC 61000-4-3
(corresponds to severity 3)
V/m 10
Electromagnetic interference emission acc. to
IEC 60947-1
CISPR 11, environment B (residential area)
Resistance to extreme climates -
Humidity
% 95
Dimensions
See Dimension drawings (dimensions in mm) (Page 151)
Installation altitude above sea level
m Up to 2,000
Mounting position
Any
Type of fixing
Direct mounting/stand-alone assembly with terminal support
1)
Permissible rated current in the case of heavy-duty starting size S0 at 10 to 40 A:
- CLASS 20E, I
emax
= 32 A,
- CLASS 30E, I
emax
= 25 A.
2)
Signaling contact 97/98 in "tripped" position: 9g / 11 ms.

Table of Contents

Related product manuals