Technical data 
  11.4 3RB30/3RB31 solid-state overload relays 
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays 
Manual, 09/2014, A5E03656507420A/RS-AA/002 
129 
Ground-fault protection (3RB31 only)
  The information refers to sinusoidal fault currents at 50/60 Hz 
•  Tripping value I
Δ
 
> 0.75 x I
motor
 
•  Operating range I 
Lower current setting < I
motor
 < 3.5 x upper current setting 
•  Response time t
trip
 (in steady-state 
condition) 
s  < 1 
Current consumption of the integrated electrical 
remote RESET (3RB31 only) 
Connection terminals 
A3, A4 
24 V DC, max. 200 mA for approx. 20 ms, thereafter < 10 mA 
Protective separation between auxiliary 
current paths
 
acc. to IEC/EN 60947-1 
V  300 
 
Auxiliary circuit – Switching capacity
  3RB30: B600, R300;  
3RB31: B300, R300