Messages and diagnostics
7.2 Function Codes
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
107
Example
Setting the bit addresses of the "Motor CW" and "Creep speed" commands to a logical one:
Address Field or slave address: The address of the 3RW5 soft starter is not entered in
the example (-).
The CRC CHECK is not entered in the example (-).
The bit addresses of the commands are:
"Motor CW": 0x8200
"Creep speed": 0x8206
The remaining bits of the byte are controlled with a logical zero (0x41).
You will find the data table for the process image output in chapter Process image output
(PIQ) (Page 150).