Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
169
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
0x9418
[37912]
high Bit4
[2326]
Alternative
stopping mode
[0 ... 6] - r/w
3)
[0]
[0] Coasting down
[1] Voltage ramp
[2] Torque control
[3] Pump stopping mode
[4] DC braking
5)
[5] Dynamic DC braking
5)
[6] Reversing DC braking
5), 6)
0x9419
[37913]
high Unsigned16
[2327]
Alternative
stopping time
0 … 360 s
[0 … 3 600]
0.1 s r/w
[100]
0x941A
[37914]
high Unsigned8
[2329]
Alternative
stopping torque
10 … 100 %
[2 … 20]
5 % r/w
[2]
0x941B
[37915]
high Unsigned8
[2332]
Alternative
dynamic braking
torque
20 … 100 %
[4 … 20]
5 % r/w
5)
[10]
0x941C
[37916]
high Unsigned8
[2331]
Alternative DC
braking torque
20 … 100 %
[4 … 20]
5 % r/w
5)
[10]
0x941D
[37917]
high Bit4
[6]
Trip class [0 ... 15] - r/w
3)
[0]
[0] CLASS 10E
[1] CLASS 20E
[2] CLASS 30E
[3] CLASS 10A
[15] CLASS OFF
0x941E
[37918]
high Unsigned16
[2211]
Remaining time for
tripping warning
limit
0 … 500 s
[0 … 500]
1 s r/w
[0]
0x941F
[37919]
high Unsigned8
[2210]
Motor heating
warning limit
0 … 99 %
[0 … 99]
1 % r/w
[0]
0x9420
[37920]
high Bit2
[5]
Response to
overload thermal
motor model
[0 ... 1] - r/w
3)
[0]
[0] Turn off without restart
[1] Turn off with restart
0x9421
[37921]
high Unsigned8
[7]
Recovery time 60 … 1 800 s
[2 … 60]
30 s r/w
3)
[10]
0x9422
[37922]
high Bit4
[9]
Temperature
sensor
[0 ... 2] - r/w
3)
[0]
[0] Deactivated
[1] Thermoclick
[2] PTC type A
0x9423
[37923]
high Bit2
[10]
Response to
overload
temperature sensor
[0 ... 2] - r/w
3)
[0]
[0] Turn off without restart
[1] Turn off with restart
[2] Warn
0x9424
[37924]
high Unsigned8
[43]
Creep speed factor
right
3 … 21
[3 … 21]
1 r/w
5)
[7]
0x9425
[37925]
high Unsigned8
[44]
Creep speed
torque right
20 … 100 %
[4 … 20]
5 % r/w
5)
[10]