Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
170 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
0x9426
[37926]
high Unsigned8
[198]
Creep speed factor
left
3 … 21
[3 … 21]
1 r/w
5)
[7]
0x9427
[37927]
high Unsigned8
[199]
Creep speed
torque left
20 … 100 %
[4 … 20]
5 % r/w
5)
[10]
0x9428
[37928]
high Unsigned16
[2337]
Current upper limit
error
50 … 400 %
[50 … 400]
5 % r/w
[0]
[0] Deactivated
0x9429
[37929]
high Unsigned16
[2338]
Current upper limit
- maintenance
demanded
50 … 400 %
[50 … 400]
5 % r/w
[0]
[0] Deactivated
0x942A
[37930]
high Unsigned8
[2340]
Current lower limit
error
20 … 100 %
[20 … 100]
5 % r/w
[0]
[0] Deactivated
0x942B
[37931]
high Unsigned8
[2341]
Current lower limit -
maintenance
demanded
20 … 100 %
[20 … 100]
5 % r/w
[0]
[0] Deactivated
0x942C
[37932]
high Unsigned32
[2250]
Active power
reference value
0 … 2 000 000 W
[0 … 2 000 000]
1 W r/w
[0]
0x942E
[37934]
high Unsigned16
[2251]
Active power upper
limit error
0 … 400 %
[0 … 400]
1 % r/w
[0]
0x942F
[37935]
high Unsigned16
[2252]
Active power upper
limit - maintenance
demanded
0 … 400 %
[0 … 400]
1 % r/w
[0]
0x9430
[37936]
high Unsigned8
[2254]
Active power lower
limit error
0 … 100 %
[0 … 100]
1 % r/w
[0]
0x9431
[37937]
high Unsigned8
[2255]
Active power lower
limit - maintenance
demanded
0 … 100 %
[0 … 100]
1 % r/w
[0]
0x9432
[37938]
high Unsigned16
[2317]
Starting time upper
limit - maintenance
demanded
0 … 400 %
[0 … 400]
1 % r/w
[0]
0x9433
[37939]
high Unsigned8
[2320]
Starting time lower
limit - maintenance
demanded
0 … 100 %
[0 … 100]
1 % r/w
[0]
0x9434
[37940]
high Bit4
[2218]
Asymmetry limit
warning
10 … 60 %
[2 … 12]
5 % r/w
[0]
[0] Deactivated
0x9435
[37941]
high Bit4
[21]
Asymmetry limit
error
10 … 60 %
[2 … 12]
5 % r/w
[6]
[0] Deactivated
0x9436
[37942]
high Unsigned8
[2220]
Ground fault limit
warning
10 … 95 %
[2 … 19]
5 % r/w
[0]
[0] Deactivated