Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
171
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
0x9437
[37943]
high Unsigned8
[2294]
Ground fault limit
error
10 … 95 %
[2 … 19]
5 % r/w
[4]
[0] Deactivated
0x9438
[37944]
high Bit4
[2242]
Emergency start [0 ... 1] - r/w
3)
[1]
[0] Disable
[1] Manually enable/disable
0x9439
[37945]
high Bit4
[2243]
Emergency run [0 ... 2] - r/w
3), 5), 7)
[0]
[0] Disable
[1] Manually enable/disable
[2] Enable
0x943A
[37946]
high Unsigned8
[194]
Input 1-Action [0 ... 45] - r/w
3)
[16]
[0] No action
[6] Operating mode manual - local
[7] Emergency start
[10] Creep speed
5)
[11] Quick-stop
[12] Reset
[16] Motor CW with PS1
[17] Motor CCW with PS1
[18] Motor CW with PS2
[19] Motor CCW with PS2
[20] Motor CW with PS3
[21] Motor CCW with PS3
[43] Motor standstill
5)
[44] Use alternative stopping mode
[45] Activate pump cleaning
0x943B
[37947]
high Unsigned8
[195]
Input 2-Action (see Input 1-Action) - r/w
3)
[0]
0x943C
[37948]
high Unsigned8
[196]
Input 3-Action (see Input 1-Action) - r/w
3)
[0]
0x943D
[37949]
high Unsigned8
[197]
Input 4-Action (see Input 1-Action) - r/w
3)
[12]