Appendix
A.2 Data tables
SIRIUS 3RW5 Modbus communication module
172 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
0x943E
[37950]
high Unsigned8
[163]
Output 1-Action [0 ... 201] - r/w
[13]
[0] No action
[1] Control source PIQ-DQ-1.0 output 1
[2] Control source PIQ-DQ-1.1 output 2
[6] Control source input 1
[7] Control source input 2
[8] Control source input 3
[9] Control source input 4
[10] Start-up
[11] Operation / bypass
[12] Run-down
[13] On time motor (RUN)
[14] Control command MOTOR ON
[16] DC braking contactor
5)
[18] Device on
[19] Operation / Run-down
[29] External bypass
5), 6)
[31] Group warning
[32] Group error
[33] Bus error
[34] Device error
[38] Ready to start for motor ON
[41] Generator operation
[42] Pump cleaning active
[43] Alternative stopping mode active
[44] CM - maintenance demanded
[45] CM - error
[180] Control source PIQ-DQ-2.0 output 3
[200] Reversing contactor right
[201] Reversing contactor left
0x943F
[37951]
high Unsigned16
[159]
Output 1 - ON
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
0x9440
[37952]
high Unsigned16
[2333]
Output 1 - OFF
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
0x9441
[37953]
high Unsigned8
[164]
Output 2-Action (see Output 1-Action) - r/w
[0]
0x9442
[37954]
high Unsigned16
[160]
Output 2 - ON
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
0x9443
[37955]
high Unsigned16
[2334]
Output 2 - OFF
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
0x9444
[37956]
high Unsigned8
[166]
Output 4-Action (see Output 1-Action) - r/w
5)
[0]
0x9445
[37957]
high Unsigned16
[162]
Output 4 - ON
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]
0x9446
[37958]
high Unsigned16
[2336]
Output 4 - OFF
delay time
0 … 6 500 s
[0 … 65 000]
0.1 s r/w
[0]