A.2 Data tables
SIRIUS 3RW5 Modbus communication module
Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
173
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
0x9447
[37959]
high Unsigned8
[2222]
Analog output -
signal type
[0 ... 3] - r/w
[0]
[0] Deactivated
[2] 4-20mA
[3] 0-10V
0x9448
[37960]
high Unsigned16
[2223]
Analog output -
measured value
[0 ... 632] - r/w
[0]
[0] Deactivated
[502] Motor temperature rise
[504] Phase current I L1 (%)
[505] Phase current I L2 (%)
[506] Phase current I L3 (%)
[510] Line voltage U L1-L2 (rms)
[511] Line voltage U L2-L3 (rms)
[512] Line voltage U L3-L1 (rms)
[513] Phase current I L1 (rms)
[514] Phase current I L2 (rms)
[515] Phase current I L3 (rms)
[518] Switching element heating
[521] Active power
[523] Power factor L1...3
[528] Phase current average (%)
[530] Phase current average (rms)
[632] Active energy import total
0x9449
[37961]
high Unsigned32
[2224]
Analog output -
range start value
0 … 4 294 967 294
[0 … 4 294 967 294]
1 r/w
[0]
0x944B
[37963]
high Unsigned32
[2225]
Analog output -
range end value
0 … 4 294 967 295
[0 … 4 294 967 295]
1 r/w
[27 648]
0x944D
[37965]
high Bit4
[2209]
Ex application [0 ... 3] - r/w
3), 6)
[0]
[0] No
[1] Yes, with complete motor protection
[2] Yes, with motor model protection
[3] Yes, with thermistor motor protection
0x944E
[37966]
high Bool
[34]
Response to
CPU/Master Stop
[0 ... 1] - r/w
[0]
[0] Switch substitute value
[1] Keep last value
0x944F
[37967]
high Bit32
[35]
Substitute value - - r/w
[0]
high
(bit 0)
Bool Substitute value:
Motor CW
[0 ... 1] - r/w
[0]
high
(bit 1)
Bool Substitute value:
Motor CCW
[0 ... 1] - r/w
[0]
high
(bit 3)
Bool Substitute value:
Reset
[0 ... 1] - r/w
[0]
high
(bit 4)
Bool Substitute value:
Emergency start
[0 ... 1] - r/w
[0]
high
(bit 6)
Bool Substitute value:
Creep speed
[0 ... 1] - r/w
5)