SIRIUS 3RW5 Modbus communication module
174 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
Register Byte Data format
[Obj. No.]
Parameter Range of values
[encoding]
In steps
of
3RW55 /
55-F
1)
[D
2)
]
Address high /
low
low
(bit 0)
Bool Substitute value:
Output 1
[0 ... 1] - r/w
[0]
low
(bit 1)
Bool Substitute value:
Output 2
[0 ... 1] - r/w
[0]
low
(bit 2)
Bool Substitute value:
Parameter set bit 0
[0 ... 1] - r/w
[0]
low
(bit 3)
Bool Substitute value:
Parameter set bit 1
[0 ... 1] - r/w
[0]
low
(bit 7)
Bool Substitute value:
Disable Quick-stop
[0 ... 1] - r/w
[0]
0x9450
[37968]
high
(bit 0)
Bool Substitute value:
Output 3
[0 ... 1] - r/w
5)
[0]
high
(bit 3)
Bool Substitute value:
Activate pump
cleaning
[0 ... 1] - r/w
[0]
low
(bit 0)
Bool Substitute value:
Manual operation
local - input
controlled
[0 ... 1] - r/w
[0]
low
(bit 1)
Bool Substitute value:
Use alternative
stopping mode
[0 ... 1] - r/w
[0]
low
(bit 2)
Bool Substitute value:
Motor standstill
[0 ... 1] - r/w
[0]
0x9451
[37969]
high Bit4
[2310]
Parameters of
CPU/master
disabled
[1 ... 2] - r/w
[1]
[1] Disable
[2] Enable
0x9452
[37970]
high Bit2
[140]
Response to
overload switching
element
[0 ... 1] - r/w
[0]
[0] Turn off without restart
[1] Turn off with restart
0x9453
[37971]
high Bit4
[232]
Response to faulty
main power
[1 ... 2] - r/w
[1]
[1] Group error only at ON command
[2] Warn
0x9454
[37972]
high Bit4
[129]
Response to preset
unequal actual
configuration of
HMI
[0 ... 4] - r/w
[0]
[0] Turn off
[1] Warn
[4] Ignore
0x9455
[37973]
high Bit4
[2344]
Pump cleaning -
mode
[0 ... 1] - r/w
[0]
[0] Deactivated
[1] Manual
low Bit4
[2345]
Pump cleaning -
start/stop
parameters
[1 ... 5] - r/w
[5]
[1] Parameter set 1
[2] Parameter set 2
[3] Parameter set 3
[5] Operating parameters