Messages and diagnostics
7.1 LED display
SIRIUS 3RW5 Modbus communication module
96 Equipment Manual, 03/2020, A5E43676481002A/RS-AC/003
"BUS" LED
State
Meaning
Lights up green
Device is performing data exchange
(3RW5 Soft Starter in Automatic mode).
Lights up red
Bus error, e.g.:
Timeout for access monitoring of the control source.
Modbus TCP cable not connected.
Switchover from old to new firmware after firmware update
(temporarily lights up)
Flashes red
Configuring error
Timeout for TCP keep-alive monitoring.
Device not performing data exchange
No Modbus TCP client connected
Off
If the Modbus TCP client is connected, no data exchange has occurred
after the 3RW5 communication module has started up.
No supply voltage available.
"LINK" LED
State
Meaning
Lights up green
There is at least one Ethernet connection between the
3RW5 communication module and a communication partner
(e.g. Ethernet switch).
Flashes green
The "node flash test" was activated.
Off
There is no Ethernet connection between the
3RW5 communication module and a communication partner
(e.g. Ethernet switch).
No supply voltage available.