Technical data
6.4 Closed-loop control
SITOP PSU100L
40 Manual, 08.2016, C98130-A7603-A1-2-7629
6.4
Closed-loop control
6EP1332-1LB00
(24 V/2.5 A)
6EP1333-1LB00
(24 V/5 A)
6EP1334-1LB00
(24 V/10 A)
6EP1336-1LB00
(24 V/20 A)
Dyn. line regulation
(U
in rated
±15 %), max.
0.3 % 0.3 % 0.3 % 0.1 %
Dyn. load regulation
(I
out
: 10/90/10 %), max.
3 % 3 % 3 % 3 %
Dyn. load regulation
(I
out
: 10/90/10 %), U
out
± typ.
2 % 2 % 2 % 1 %
Load-step settling time
10 to 90 %, typ.
0.5 ms 0.4 ms 0.5 ms 1 ms
Load-step settling time
90 to 10 %, typ.
0.7 ms 0.4 ms 0.7 ms 1 ms
6.5
Protection and monitoring
6EP1332-1LB00
(24 V/2.5 A)
6EP1333-1LB00
(24 V/5 A)
6EP1334-1LB00
(24 V/10 A)
6EP1336-1LB00
(24 V/20 A)
Output overvoltage
protection
< 33 V < 33 V < 33 V < 33 V
Current limitation, typ.
2.6 A
5.25 A
-
23.4 A
Properties of the out-
put/short-circuit proof
Yes
Short-circuit protection Electronic trip, automat-
ic restart
Electronic trip, automat-
ic restart
U-I characteristic U-I characteristic
Continuous short-circuit
current / rms val-
ue / typical
- - 12.6 A 23.9 A
6.6
MTBF
6EP1332-1LB00
(24 V/2.5 A)
6EP1333-1LB00
(24 V/5 A)
6EP1334-1LB00
(24 V/10 A)
6EP1336-
1LB00(24 V/20 A)
M
ean
T
ime
B
etween
F
ailures
SN29500:
> 2100000 h at
40 °C,rated load,
24-hour operation
SN29500:
> 1600000 h at 40 °C,
rated load, 24-hour
operation
SN29500:
> 1400000 h at 40 °C,
rated load, 24 h opera-
tion
SN29500: > 500000 h
at 40 °C, rated load,