Safety, approvals, EMC
7.2 Test voltage
SITOP PSU100L
44 Manual, 08.2016, C98130-A7603-A1-2-7629
7.2
Test voltage
Figure 7-1 Test voltage without auxiliary contact diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another (L, N)
Connect the output terminals and PE together
Test (C)
Measure the output terminals with respect to PE
Table 7- 1 Test voltage
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 VDC
2200 VDC
700 VDC
60 s
3000 VAC
1500 VAC
500 VAC
Production test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Field test
1 s
2200 VDC
2200 VDC
500 VDC
1 s
1500 VAC
1500 VAC
350 VAC
Remark:
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: <100 mA