Safety, approvals, EMC
7.2 Test voltage
SITOP PSU100L
44 Manual, 08.2016, C98130-A7603-A1-2-7629
Figure 7-1 Test voltage without auxiliary contact diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another (L, N)
● Connect the output terminals and PE together
Test (C)
● Measure the output terminals with respect to PE
Table 7- 1 Test voltage
Type test
Production test
Field test
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: <100 mA