Technical data
6.2 Output
SITOP PSU100L
34 Manual, 08.2016, C98130-A7603-A1-2-7629
Figure 6-1 Power failure buffering
6.2
Output
6EP1332-1LB00
(24 V/2.5 A)
6EP1333-1LB00
(24 V/5 A)
6EP1334-1LB00
(24 V/10 A)
6EP1336-1LB00
(24 V/20 A)
Output
Regulated, isolated DC voltage
Rated voltage U
out rated
DC
24 V
Total tolerance, static ±
3 %
3 %
3 %
3 %
Static line regulation, ap-
prox. ±
0.1 % 0.1 % 0.1 % 0.1 %
Static load regulation, ap-
prox. ±
0.5 % 0.5 % 0.5 % 0.5 %
Residual ripple
Peak-peak, max.
150 mV 150 mV 150 mV 150 mV for a band-
width of 20 MHz
Residual ripple peak-peak,
typ.
10 mV 50 mV 50 mV 80 mV for a band-
width of 20 MHz
Spikes peak-peak, max.
(bandwidth, 200 MHz)
240 mV 240 mV 240 mV -
Spikes peak-peak, typ.
(bandwidth, approx.
20 MHz)
50 mV 150 mV 150 mV 200 mV
Adjustment range
22.8 - 26.4 V
22.8 - 28 V
Product function/output
voltage can be adjusted
Yes
Adjusting the output voltage Using a potentiome-
ter
Using a potentiome-
ter
Using a potentiome-
ter
Using a potentiome-
ter
Operating display
LED green for "24 V O.K."
Response when switching
on/off
U
out
overshoots by approximately 4 %