Ambient conditions
SITOP PSU100L
48 Manual, 08.2016, C98130-A7603-A1-2-7629
6EP1332-1LB00 (24 V/2.5 A)
6EP1333-1LB00 (24 V/5 A)
6EP1334-1LB00 (24 V/10 A)
6EP1336-1LB00 (24 V/20 A)
Damaging gases Tested according to:
• EN 60068-2-42 sulfur dioxide
• EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
• 1080 - 795 hPa (-1000 - 2000 m)
• For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-5 Mounting height derating (Page 22)
• Overvoltage category:
III to 2000 m (EN 50178)
II from 2000 m to 6000 m (EN 50178)
II to 2000 m (EN 60950-1)
I from 2000 m to 6000 m (EN 60950-1)
Storage:
• 1080 - 660 hPa (-1000 - 3500 m)