Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
17
Signaling
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
Red LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
Latching shutdown Latching shutdown Latching shutdown
LED flashing red
Signaling contact,
contact (13, 14) opened
(quiescent position)
- - Overtemperature → power
OFF/ON after 3 min
Signaling
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
Green LED lit
Signaling contact,
contact (13, 14) closed
Normal operation, output
voltage > 10 V ± 0.5 V
Normal operation, output
voltage > 20 V ± 0.5 V
Normal operation, output
voltage > 20 V ± 1 V
LED off
Signaling contact,
contact (13, 14) opened
(quiescent position)
Supply voltage missing
Supply voltage missing
Supply voltage missing
Yellow LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
Overload, output voltage
< 10 V ± 0.5 V (only in the
"constant current" mode)
Overload, output voltage
< 20 V ± 0.5 V (only in the
"constant current" mode)
Overload, output voltage
< 20 V ± 1 V
Yellow and green LEDs lit
Signaling contact,
contact (13, 14) closed
Phase failure, output voltage
O.K.
Phase failure, output voltage
O.K.
-
Red LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
Latching shutdown Latching shutdown Latching shutdown
LED flashing red
Signaling contact,
contact (13, 14) opened
(quiescent position)
- - Overtemperature → power
OFF/ON after 3 min