Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200/3800 3ph
86 Manual, 05.2018, C98130-A7638-A1-6-7629
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals, signaling contact, remote and PE with one another
Test (C)
● Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1 Test voltage for 6EP3436-8SB00-0AY0, 6EP3446-8SB10-0AY0, 6EP3446-8SB00-0AY0, 6EP3424-8UB00-
0AY0 and 6EP3436-8UB00-0AY0
Type test
Production test
Field test
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA