EasyManua.ls Logo

Siemens SITOP PSU8200 24 V/20 A - Protection and monitoring

Siemens SITOP PSU8200 24 V/20 A
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.5 Protection and monitoring
SITOP PSU8200/3800 3ph
78 Manual, 05.2018, C98130-A7638-A1-6-7629
6.5
Protection and monitoring
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP1437-3BA10
(24 V/40 A)
6EP3437-8SB00-0AY0
(24 V/40 A)
Output overvoltage protec-
tion
< 35 V (PR1)
< 31.8 V (from PR2)
< 31.8 V < 31.8 V
Current limitation, typ.
23 A
44 A
50 A
Property of the output: short-
circuit proof
Yes Yes Yes
Short-circuit protection Optional constant current
characteristic approx. 23 A
or latching shutdown
Optional constant current
characteristic approx. 44 A
or latching shutdown
Optional constant current
characteristic approx. 50 A
or latching shutdown
Continuous short-circuit
current: rms value, typ.
Remark
23 A
Overload capability 150 %
I
out rated
up to 5 s/min
44 A
Overload capability 150 %
I
out rated
up to 5 s/min
50 A
Overload capability 150 %
I
out rated
up to 5 s/min
Overload / short-circuit indi-
cator
Yellow LED for "overload",
red LED for "latching shut-
down"
Yellow LED for "overload",
red LED for "latching shut-
down"
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3447-8SB00-0AY0
Output overvoltage protec-
tion
< 48 V < 60 V < 60 V
Current limitation, typ.
14 A
11 A
25 A
Property of the output: short-
circuit proof
Yes Yes Yes
Short-circuit protection Optional constant current
characteristic approx. 14 A
or latching shutdown
Optional constant current
characteristic approx. 11 A
or latching shutdown
Optional constant current
characteristic approx. 25 A
or latching shutdown
Continuous short-circuit
current: Rms value, typ.
Remark
14 A
Overload capability 150 %
I
out rated
up to 5 s/min
11 A
Overload capability 150 %
I
out rated
up to 5 s/min
25 A
Overload capability 150 %
I
out rated
up to 5 s/min
Overload / short-circuit indi-
cator
Yellow LED for "overload",
red LED for "latching shut-
down"
Yellow LED for "overload",
red LED for "latching shut-
down"
Yellow LED for "overload",
red LED for "latching shut-
down"
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
Output overvoltage protec-
tion
< 18 V < 31.8 V < 31.8 V
Current limit, typ.
22 A
19 A
50 A
Property of the output: short-
circuit proof
Yes Yes Yes

Table of Contents