EasyManua.ls Logo

Siemens SITOP PSU8200 24 V/20 A - Page 19

Siemens SITOP PSU8200 24 V/20 A
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description, device design, dimension drawing
2.5 Change-over switch
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
19
For 6EP3437-8UB00-0AY0 (24 V/40 A)
Switch
ON
OFF
A
influences the output
characteristic in the
load range
Parallel operation:
"Soft" characteristic curve (see
Figure 6-20 Output
characteristic 6EP3437-8UB00-0AY0 parallel opera-
tion (B OFF) (Page 67)) for the parallel operation of
two or more devices: The output voltage falls with
increasing output current.
This means that for full output current the highest
output voltage can normally no longer be attained.
Single operation:
delivery condition
"Hard" characteristic curve (see Figure 6-
11 Output characteristic 6EP3437-
8UB00-0AY0 single operation (B OFF)
(Page 64
)) for normal operation (single
operation): The output voltage is inde-
pendent of the output current.
B
is used to switch over
the output current
Rated current:
I
out rated
= 30 A, no latching shutdown
see
Figure 6-29 Output characteristic 6EP3437-
8UB00-0AY0 single operation (Page 70)
Rated current:
delivery condition
I
out rated
= 40 A, no latching shutdown
Note
Selector switches may only be activated when the device is switched off.