Page EN-10 SITRANS LC300 – QUICK START MANUAL A5E32268590
mmmmm
English
LC300 Menu Functions
Use the rotary switch and the push-buttons to set the display and programming values for your
application.
Maintenance
SITRANS LC300 requires no maintenance or cleaning under normal operating conditions. Even
with significant build-up on the SITRANS LC300 probe, the level controller will continue to
operate.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
Rotary
Switch
Position
0 1 2 3 4 5
Display
Read PV
(pF)
Read LRV (pF)
(0% level)
Read URV (pF)
(100% level)
Read mA loop-
current
Diagnostics Damping
Up button
Increase LRV Increase URV
Set fault protection
setting to 22 mA
Product
Version
Increase
Damping
Down
button
Decrease LRV Decrease URV
Set fault protection
setting to 3.6 mA
Decrease
Damping
Both
buttons
Set LRV from PV Set URV from PV
Disable fault
protection
Reset/
Acknowledge
Fault
Set Damping
to 1.00
Note: Build-up of material on the active shield area has little or no effect on the
performance of the SITRANS LC300.